| Last update date |
15/05/2026 |
|
|
|
| Associated operating year |
2025 |
|
|
|
| Key performance information |
|
|
|
|
| IT power installed |
765 |
kW |
|
|
| Center’s total floor aera |
1638 |
m2 |
|
|
| Server room floor aera |
642 |
m2 |
|
|
| Total energy consumption |
4935126 |
kWh |
|
|
| IT energy consumption |
3112381 |
kWh |
|
|
| PUE |
1.586 |
|
|
|
| WUE |
57 |
|
|
|
| REF |
0.015 |
|
|
|
| ERF |
0.000 |
|
|
|
| Information subject to certification or third-party audit |
No |
|
|
|
| Implementation of an Energy Management System |
No |
|
|
|
| Joining European Code of Conduct on Data Centre Energy Efficiency |
Yes |
|
|
|
| National power grid integration |
No |
|
|
|
| “Waste heat ready” qualification |
No |
|
|
|
| Additional performance information |
|
|
|
|
| Electrical infrastructure redundancy |
N |
|
|
|
| Cooling infrastructure redundancy |
N |
|
|
|
| Backup generators energy consumption |
0 |
kWh |
|
|
| Average battery capacity |
0 |
kW |
|
|
| Total water consumption |
180274 |
m3 |
|
|
| Drinking water consumption |
60 |
m3 |
|
|
| Reused waste heat |
0 |
kWh |
|
|
| Average temperature of waste heat |
31 |
°C |
|
|
| Average intake air setpoint temperature for IT equipment |
24 |
°C |
|
|
| Type of refrigerant used |
F-gas:R-410A;Natural:R-729 (air) (free cooling);Natural:R-718 (water) |
|
|
|
| Cooling Degree Day |
122 |
|
|
|
| Total renewable energy consumption |
47283 |
kWh |
|
|
| Renewable energy consumption with Guarantee of Origin |
0 |
kWh |
|
|
| Energy consumption covered by renewables PPAs |
0 |
kWh |
|
|
| Consumption of renewable energy produced on-site |
47283 |
kWh |
|
|
| Server capacity |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Server coverage |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Storage capacity |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Storage coverage |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Network bandwidth (inbound) |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Network bandwidth (outbound) |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Data exchange volume (inbound) |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| Data exchange volume (outbound) |
Confidential |
Protection du Potentiel Scientifique et Technique |
|
|
| National power grid integration (details) |
|
|
|
|